◆Product: JY-IIB Oil-spill Static Protector
It has the function of static conducting and overfill prevention and is to be used in the loading system of liquid chemical products. It can be interlocked with automatic control system, when the
liquid level reaches the sensor or there is ineffective grounding, it will send out acousto-optic alarm and output signal to stop the valve and pump to prevent overfill and ensure static grounding.
◆Advantages:
1. Output signal and interlock with computer system. 2. The sensor has self-checking function. It gives malfunction alarm when it is at fault. 3. Provide on-site acousto-optic alarm, clear and visible.
◆Parameters:
1. Explosion proof class: Exdia II BT42.Power: 220VAC±10% 3.Output signal: 1.0A,24VDC or0.5A,125VAC 4. Optional output signal: 5.0A, 30VDC or 5.0A, 250VAC 5. Working current: 15mA6. Response time: < 2s 7. Detection resistance: < 60Ω8. Temperature: -40℃-60℃ |